header image

Contactor

DP Contractor for HVAC, recently added to TelcoMotion's HVAC product group, offers features of up to 50% of cost and space savings compared to the IEC contactor, easy installation and easy maintenance.  Snap on accessories and universal mounting plate available.  Regular stock available in States guarantees same day shipping with no minimum order quantity. UL508/IEC/ARI 780/790 compliance.

Features

  • Screw and box lug terminals are interchangeable on 3 poles series
  • Maximum of three auxiliary contacts blocks available
  • Snap on accessories
  • Universal mounting plate
  • 15%~50% cost savings compared to the IEC contactors
  • 30%~40% space savings compared to the IEC contactors
  • Easy installation
  • Easy maintenance
  • Standards Compliance : UL 508, IEC 60947-1 & 60947-4-1, ARI 780/790 (Air Conditioning and Refrigeration Institute)

Applications

  • HVAC
  • POWER SUPPLIES
  • FOOD PROCESSING
  • LIGHTING
  • POOL AND SPA
  • PUMPS, HOISTS, AND CRANES
  • AGRICULTURE
 Catalog Number  YB09-1020  YB09-1520  YB09-2020  YB09-1025  YB09-1525  YB09-2025  YB09-1030  YB09-1530 YB09-2030  YB09-1040 YB09-1540   YB09-2040
 Photos  DPA1020  DPA1525  DPA2030  DPA2040
 Number of Poles  1  1+ shunt  2  1  1+ shunt  2  1  1+ shunt  2  1  1+ shunt  2
 Terminal  SCREW/LUG  SCREW/LUG  SCREW/LUG  SCREW/LUG
 Rated Insulation Voltage (Ui) UL/IEC  600/660
 Operation Voltage (Ue) UL/IEC  600/660
 Duty Thermal Current (Ith) UL/IEC  30  35  40  50
 AIR CONDITIONING & REFRIGERATION INSTITUTE Standard 780/790  Full load Amps (FLA)  20  25  30  40
 Locked Rotor Amps (LRA)  Single Phase  240-277V  120  150  180  240
  A  480V  100  125  150  200
   600V  80  100  120  160
 Resistance Load (RES) A  30  35  40  50
 UL 508  Full Load Current (FLA)  Single Phase  120V  1.5Hp/20A  2Hp/24A  2Hp/24A  3Hp/34A
 240/277V  3Hp/17A  3Hp/17A  5Hp/28A  7.5Hp/40A
 IEC 60947-1 IEC60947-4-1  Rated Current (A)  220V  20  25  30  40
 AC 7a, AC 8a  380V  20  25  30  40
   Resistance Load (RES) A  32  35  40  50
 Weight (Lbs.)  0.51  0.51  0.66  0.51  0.51  0.66  0.51  0.51  0.66  0.51  0.51  0.66
 Weight (Lbs.)        0.51  0.51  0.66  0.51  0.51  0.66  0.51  0.51  0.66  0.51  0.51  0.66
 Catalog Number  YB09-3020  YB09-3025  YB09-3030 YB09-3040
 Photos  DPA3020  DPA3025  DPA3030  DPA3040
 Number of Poles  3  3  3  3
 Terminal  SCREW/LUG  SCREW/LUG  SCREW/LUG  SCREW/LUG
 Rated Insulation Voltage (Ui) UL/IEC  600/660
 Operation Voltage (Ue) UL/IEC  600/660
 Duty Thermal Current (Ith) UL/IEC  30  35  40  50
 AIR CONDITIONING & REFRIGERATION INSTITUTE  Full load Amps (FLA)  20  25  30  40
 Standard 780/790  Locked Rotor Amps (LRA)  Single Phase  240-277V  120  150  180  240
   A  480V  100  125  150  200
     600V  80  100  120  160
   Resistance Load (RES) A  30  35  40  50
 UL 508    Single Phase  120V  1.5Hp/20A  2Hp/24A  2Hp/24A  3Hp/34A
 Full Load Current (FLA)  240/277V  3Hp/17A  5Hp/28A  5Hp/28A  7.5Hp/40A
   Three Phase  440/480V  5Hp/14A  5Hp/14A  7.5Hp/21A  15Hp/34A
 Rated Current  220/240V  7.5Hp/22A  10Hp/28A  10Hp/28A  10Hp/28A
 (A)  440/480V  7.5Hp/11A  15Hp/21A  15Hp/21A  20Hp/27A
   550/600V  7.5Hp/9A  20Hp/22A  20Hp/22A  25Hp/27A
 IEC 60947-1, IEC60947-4-1  Rated Current (A)  220V  20  25  30  40
 AC 7a, AC 8a  380V  20  25  30  40
   Resistance Load (RES) A  32  35  40  50
 Weight (Lbs)  0.95  0.95  0.95  0.95
 Weight (Lbs)        0.95  0.95  0.95  0.95

To ensure the electric motors you choose are perfectly suited for your needs, our team is available to guide you through your motor selection process. Call 281-855-2218 and one of our electric motor experts will assist you, or push the Electric Motor Request Button.